BRAND | S+S REGELTECHNIK |
Product | 1101-1192-0009-900 / THERMASGARD® ATM2-SD-I |
Description | outdoor temperature/humidity-room temperature transmitter |
Internal code | IMP4988160 |
Weight | 0.177 |
Technical specification | power consumption < 1.0 W/ 24V DC < 2.2 VA/ 24 V AC power supply 15... 36 V DC depending on the load, residual ripple stabilized ± 0.3 V sensor Pt1000, DIN EN 60751, class B (Perfect Sensor Protection) circuit type 2 or 3-wire connection precision typical ± 0.2 K at +25 °C Ambient temperature Transmitter —30... +70 °C Process connection by means of screws Protection tube stainless steel V4A (1.4571), diameter 6 mm, NL = 65 mm electrical connection 0.14 - 1.5 mm², via screw terminals cable fitting M 16 x 1.5; with strain relief, replaceable max. inner diameter 10.4 mm allowable humidity < 95% RH, non-condensing air protection class III (according to EN 60 730) Measurement ranges Multi-range switching with 8 switchable measurement ranges (other measurement ranges optional) Operating range —30... +70 °C with manual zero point correction (± 10 K) cable connection plastic cable screw (M 16 x 1.5; with strain relief, replaceable, inner diameter 10.4 mm) or M12 connectors in accordance with DIN EN 61076-2-101 (optional on request) housings made of plastic, UV-resistant, Material polyamide, 30% glass ball reinforced, color traffic white (similar to RAL 9016), with snap-on lid Case dimensions 72 x 64 x 37.8mm (Tyr 01) Protection class IP 54 (according to EN 60 529) * standards CE compliance, electromagnetic compatibility in accordance with EN 61326, according to EMC Directive 2014/ 30/EU |