BRAND | Thermokon |
Product | DPA7000+ LCD AA MultiRange / 667128 |
Internal code | IMP5131114 |
Weight | 0.41 |
Custom code | 90262020 |
Technical specification | <p>Differential temperature measurement pressure, Vol — 4.. 20 mA<br>output: 2x 4.. 20 mA (differential pressure and flow rate)<br>Differential pressure measurement range: 0.. +1000 | 0.. +1500 | 0.. +2000 | 0.. +3000 | 0.. +4000 | 0.. +5000 | 0.. +7000 Pa (standard:<br>0.. +7000 Pa), adjustable on the device<br>Flow rate measurement range: 0.. +750,000 m³/h, adjustable via Thermokon + App<br>Measurement units: pressure in Pa or inchWC, flow rate in m³/h or cfm<br><2000 Pa, ±25 Pa bei Messbereich >Pressure accuracy: ±10 Pa with a measurement range of 2000 Pa<br>Voltage supply: 15.. 35 V =<br>Display: LCD 29x35 mm with RGB backlight, configurable via Thermokon + App<br>USE-L shock-proof and shatterproof housing with hinged cover (PC, pure white, IP65)<br>Removable cable entry (M20 flex, replaceable) and removable plug terminal (max. 2.5 mm²),<br>Output protection circuit (reverse polarity protected)<br>Screw connection on a flat surface, prepared for snap mounting on standard TS35 support rail (35x7.5 mm)<br>incl. mounting base, mounting screws, 2 m PVC connection hose and pressure connection<br></p> |